<acronym id="kecks"></acronym>
<rt id="kecks"><small id="kecks"></small></rt>
Guangzhou Kingrise Enterprises Co., Ltd.
All Products
KE7303
Portable Three Phase Standard Meter
Accuracy : 0.05 / 0.1, Test method : terminal input or clamp CT input, test the error of three phase energy meters and feild electrical parameters of power grid

Highlight

2           Calibrate the error of all electricity energy meters, checking the constant of the energy meter

2        Simultaneous checking of the primary meter and the secondary meter in the same loop, or simultaneously checking of the active power meter and reactive power meter inthe same loop

2        Measure voltage, current, frequency, power, power factor and phase angle

2        Simultaneous measure and display waveforms of three phase voltage and current

2        Detectthe error change of the clamp automatically; ensure the accuracy stability ofthe clamp and the instrument in the long run.

2        Measureratio of CT, VA burden of the metering loop from VT and CT secondary terminals.

2        Allocate clamp of 20A, 100A, 500A, 1000A to directly measure the comprehensive error

2        Measurethe 2nd – 51st harmonics of current and voltage

2        Display vector diagram, judge the wiring right or wrong automatically

2        Read the information of energy meter with barcode scanner (optional)

2        Battery, test lead power or external power for choices

2        Communicate with PC, download calibration data through USB flash disk, RS-232 or bluetooth 

2        Firmware can be upgraded through removed disk by users themselves

2        Save and browse the testing data, data storage quantity is 1000 group 

Main specifications

 

KE7303-0.05

KE7303-0.1

Voltage measurement

Voltage range

0V – 480V

Accuracy

±0.05%

±0.1%

Harmonics

2nd- 51st

Current measurement

Current range

Terminal input

0.1A – 10A

Clamp input

5A、20A、100A、500A、1000A、2000A、3000A

Accuracy

Terminal input

±0.05%

±0.1%

Clamp input

±0.2%5A)、±0.5% (others)

Harmonics

2nd- 51st

Power measurement

Active power

Terminal input

±0.05%

±0.1%

Clamp input

±0.2%5A)、±0.5% (others)

Reactive power

Terminal input

±0.05%

±0.1%

Clamp input

±0.2%5A)、±0.5% (others)

Energy measurement

Active energy

Terminal input

±0.05%

±0.1%

Clamp input

±0.2%5A)、±0.5% (others)

Reactive power

Terminal input

±0.05%

±0.1%

Clamp input

±0.2%5A)、±0.5% (others)

Phase measurement

Phase range

0 -- 360°

Accuracy

±0.05°

±0.1°

Frequency measurement

Frequency range

45Hz – 65Hz

Accuracy

±0.05Hz

Pulse output

High frequency outputCH

3.6×107imp / kWh

Low frequency outputCL

3.6×104imp / kWh

Pulse input

Input channel

2

Input frequency

Max. 100Hz

Others

Power supply

Build-in rechargeable battery, external power supply, powered from the tested terminal

Dimensions

154mm×249mm×58mm

Weight

1.8kg

 

 